8H30 – 12H30 / 14h – 17H30 | from Monday to Friday
contact@tacquet-industries.fr
03 21 13 13 00
Our teams carried out a DN350 PN10 hot tap on a DN500 potable water header, with no service interruption.
Following the installation by the client of a welded DN350 flange connection and a full-bore valve, we proceeded with the hot tapping operations under pressure.
The tapping machine was mounted onto the valve and subjected to a nitrogen tightness test to ensure full safety before drilling. The cut, with a diameter of 324 mm, was performed with precision, and the coupon was returned to the client at the end of the intervention.
In the case of rolled or spiral-welded headers, an internal reinforcement is systematically installed to prevent any equipment blockage and ensure safe execution.
This operation highlights our expertise in large-diameter live tapping, combining technical precision, safety, and compliance with sanitary standards for potable water networks.
Intervention du 22 octobre 2024